Why have headaches over firestopping?

Let us deal with it for you.
Licensed and Bonded
Terms

Glossary of Common Terminology. 

This list is continuously growing. It includes terms that are found in firestopping, smoke, sound blocking.


  • 07270:  Firestop Section of the Architecture Specifications Guide, pre 95 format
  • 07840:  Firestopping and Smoke Protection” section of the architectural specifications guide CSI 95 format
  • 07 84 00:  "Firestopping" CSI format 2004
  • 4991 Installer:  An installation company that has meet and been certified under FM 4991 standard.
  • Ablative: Materials that provide fire resistance by gradually eroding to the flame front at a known or predictable rate.
  • ABS:  Abbreviation or Acronym for Acrylonitrile-Butadiene-Styrene pipe. Plastic pipe installed usually for drain, waste, vent and sewage.
  • ABS Pipe: Plastic (Acrylonitrile Butadiene Styrene) pipe used for water distribution, drain, waste, and vent.
  • Acoustical:  The properties of a material to absorb or reflect sound (adjective) acoustically, (adverb).
  • Acoustical Environment:  The acoustical characteristics of a space or room influenced by the amount of acoustical absorption, or lack of it, in the space.
  • Adhesive Failure:  failure of the bond between the sealant, adhesive, or coating and substrate surface
  • Ambient Noise:  Ambient noise encompasses all sound present in a given environment, being usually a composite of sounds from many sources near and far.
  • Annular Space Requirements Per NFPA Std. #13:   In section 4-5.4.3.4, it requires that sprinkler pipes in seismic areas, have a minimum annular space of 1-inch for pipes 1" through 3-1/2" and 2- inches for pipes 4" and larger. Exceptions to this standard do exist. Please consult NFPA Standard #13 for details.
  • Annulus (Annular measurement or space): The gap between the penetrating item and the edge of the hole. In a given penetration, the measurement from the outside diameter (O.D.) of the pipe to the inside diameter (I.D.) of the hole.
  • Approved Methods:  A term used to refer to the through-penetration firestop systems that have been tested and meet test criteria of ASTM E 814 by an independent, recognized laboratory. Additionally, an authority having jurisdiction may also make specific product evaluation and determine compliance with appropriate standards. Products alone are not tested systems/approved firestop methods unless tested to ASTM E 814 and classified for use in the specific application. 
  • Architectural Acoustics:  The control of noise in a building space to adequately support the communications function within the space and its effect on the occupants. The qualities of the building materials used to determine its character with respect to distinct hearing.
  • Area Effect:  Acoustical materials spaced apart can have greater absorption than the same amount of material butted together. The increase in efficiency is due to absorption by soft exposed edges and also to diffraction of sound energy around panel perimeters.
  • Assembly Rating:  The rating, in hours, for a wall or floor assembly’s ability to prevent the passage of heat or hot gases and to limit a temperature rise to not more than 250°F (120°C) on average or 325°F (160°C) at any one point.
  • ASTM:  Abbreviation or Acronym for American Society for Testing and Materials.
  • ASTM E 119:  Fire test method, “Fire Tests of Building Construction and Materials,” conducted to evaluate the ability of a fire-resistive floor or wall assembly to perform its barrier function, resisting the passage of heat, flames, hot gases, and smoke in a fire situation.
  • ASTM E 136:  Test Method for Behavior of Materials in a Vertical Tube Furnace at 750°C.  This test evaluates the ability of a material to be considered as non-burning.  Weight loss of the test sample and heat rise due to the flammable content of the sample are key criteria.  It is not a fire resistance test.  This standard is inappropriate for inclusion in fire stopping specifications because it favors inorganic, generally rigid or brittle materials.
  • ASTM E 1399:  Test Method of Measuring the Minimum and Maximum Joint Widths of Architectural Joint Systems.  This test is used to condition a joint assembly prior to exposure to an ASTM E119 fire-test.
  • ASTM E 1966:  Test Method for Fire-Resistive Joint Systems.  This test is used to evaluate the performance of a joint after a cyclic movement test and fire-exposure test.  Ul2079 roughly equates to this test procedure.
  • ASTM E 84:  “Surface Burning Characteristics of Building Materials” or ASTM E 84 usually refers to the flame spread or smoke developed characteristics of a product (i.e. wallpaper, coatings, carpet, etc.). NOTE: ASTM E 84 is not the same as ASTM E 814, “Fire Tests of Through Penetration Firestops.” 
  • ASTM E 814:  “Fire Tests of Through Penetration Firestops” or ASTM E 814 is the complementary test to ASTM E 119 that evaluates penetrations through a tested, fire-resistive (ASTM E 119 tested) wall or floor assembly. The test involves a standard time-temperature curve, a hose stream test and assigns ratings based on “T” (temperature rise) and “F” (flame occurrence through the firestop/penetration). The objective of specifying this type of system is to return the floor or wall to the compartment's original fire rating. An “L” (air leakage) rating can also be assigned. Air leakage simulates smoke movement through a penetration, measured in cubic feet per minute for authorities having jurisdiction to make judgments. 
  • Attenuation:  The reduction of sound energy as a function of distance traveled.
  • Audiometer:  An instrument for measuring hearing acuity.
  • Authority Having Jurisdiction:  The final authority who writes the "Certificate of Occupancy Permit” in a municipality. This can be the building code official/inspector or fire inspector. Since each municipality is different, the “authority having jurisdiction” may also be different from town to town. Check with local officials to verify who has final jurisdiction. Industrial facilities and hospitals may have other “jurisdictions.”
  • Autobonding:  The ability of fresh material to adhere to previously installed (cured or dried) material of same type.
  • A-Weighted Sound Level:  A measure of sound pressure level designed to reflect the response of the human ear, which does not respond equally to all frequencies. To describe sound in a manner representative of the human ear’s response it is necessary to reduce the effects of the low and high frequencies with respect to the medium frequencies. The resultant sound level is said to be A-weighted, and the units are dBA. The A-weighted sound level is also called the noise level. Sound level meters have an A-weighting network for measuring A-weighted sound levels.
  • AWG:  Abbreviation for American Wire Gauge – used in combination with a number to identify a particular size wire. 
  • Backer Rod: A combustible polyurethane or polyethylene foam material used to provide support for gunned or troweled sealant within walls or floors.
  • Backing Material (Forming Material, Packing Material) :   Material used in firestop systems (e.g. mineral wool, backer rod, CF 128 foam) to set the depth and provide support for the fill, void cavity material.
  • Baffle:  A free hanging acoustical sound absorbing unit. Normally suspended vertically in a variety of patterns to introduce absorption into a space to reduce reverberation and noise levels.
  • Boominess:  Low frequency reflections. In small rooms, acoustical panels with air space behind can better help control low frequency reflectivity.
  • Bottom-Of-Wall:  The gap between the bottom of a wall assembly and the upper surface of the floor assembly below it.
  • British Thermal Unit (Btu): The heat required to raise the temperature of one pound of water through 1 degree Fahrenheit at atmospheric pressure.
  • Building Codes: Model building codes are adopted by each municipality from the major code organizations. The major code authorities are BOCA (Building Officials and Code Administrators) primarily in the Midwest, ICBO (International Council of Building Code Officials) in the West and Indiana, and SBCCI (Southern Building Code Congress, International) in the South. The local municipality or state can choose which major building code is adopted, or can adapt its own.
  • Building Officials and Code Administrators (BOCA) :   Publishes National Building Code (NBC). It is principally used in the Midwest and Northeastern portions of the United States.
  • Building Separation Wall:  A fire-resistance rated wall, having protected openings, which restricts the spread of fire and extends continuously from the foundation to or through the roof.
  • Burn: To undergo combustion.
  • Burn Patterns: The characteristic configuration of char left by fire. Burn patterns are influenced by wind direction, length of exposure, and type of fuel. They can be used to trace a fire’s origin. (Also called fire tracks).
  • Butt Joint:  The point within the joint treatment where two or more lengths of a joint system or a joint system  component material are joined.
  • Butt Vertical Joint: The meeting of two vertical veneers whose joint faces are parallel.
  • Cable Tray:  An opened or closed steel ladder or metal tray, which is used to support runs of multiple cables strung throughout buildings.
  • Calcination / Calcined:  To heat to a high temperature but without fusing in order to drive off volatile matter or to affect changes (asoxidation).
  • CAN/ULC-S115: “Standard Method of Fire Tests of Firestop Systems”
  • Ceramic Fiber:  High temperature man made fiber (45% alumina, 53% silica) used as insulating material where high service temperatures are required. Design service use 2300 deg. F (1260 deg. C) melting 3200 deg. F (1760 deg. C) available in 4, 6 and 8 pcf density batts/blankets. Some times used instead of mineral wool for 3 and 4-hour systems. 
  • Char:  A grayish black, crusty material formed by burning organic type sealants.
  • Classification:   a series of procedures which protect the consumer and assure that the product is safe
  • Classified:  UL terminology for products that in and themselves have no listing or approval.  Products that are UL classified have predictable ratings or performance only after installation in a construction condition similar to UL published designs.
  • Closed Piping System:   Piping system which is completely enclosed, usually carrying fluids under pressure. Examples: hot/cold water distribution, sprinkler piping, chilled water supply and return.
  • Closed System:  usually refers to a piping system for water distribution when the pipe is full, under pressure and closed at pipe termination. In some jurisdictions electrical conduit is considered closed.
  • Cloud:  In acoustical industry terms, an acoustical panel suspended in a horizontal position from ceiling/roof structure. Similar to a baffle but in a horizontal position.
  • CMU:  Concrete Masonry Unit. Usually hollow, pre-cast concrete blocks used to construct walls.
  • Cocktail Party Effect:  Sound in a noisy crowded room generated mostly by conversation. Levels rise and fall as people compete with one another to be heard. Perception of speech can be nearly impossible in high levels of noise.
  • Cohesion:  the internal strength of an adhesive or sealant
  • Cohesive Failure:  failure that occurs when an adhesive, sealant, or coating is ruptured
  • Collars (Pipe Collars) - A one-piece prefabricated device consisting of intumescent strips and a restricting metal collar. Used on plastic pipes to direct the intumescent expansion.
  • Combustible:  Capable of undergoing combustion.
  • Combustible Construction: That type of construction that does not meet the requirement for noncombustible construction. Combustible means that a material fails to meet the acceptable criteria of ASTM E 136 (Standard Method of test for Determination of Non-Combustibility in Building Materials).
  • Combustible Penetrants:  Pipes, cable, or other penetrants that may burn or melt out during a fire.
  • Combustion:  A chemical process of oxidation that occurs at a rate fast enough to produce heat and usually light, either as a glow or flame.
  • Concentric: Having a common center like a penetrating item centered in the middle of a through-penetration hole.
  • Construction Joint:  1.A joint where two successive placements of concrete meet. 2. A separation provided in a building which allows its component parts to move with respect to each other. The cause of such movement may be thermal, seismic, or wind loading.
  • Continuous Point of Contact:  An area where no gap exists between a penetrating item and the edge of the hole.
  • Control Joint:  a joint that acts to regulate the location and degree of cracking or separation resulting from the dimensional change of different elements within a structure
  • CPVC:  Acronym for Post-Chlorinated Polyvinyl Chloride.  A combustible thermoplastic resin used in the manufacture of certain nonmetallic pipes used primarily of sprinkler applications.
  • CPVC Pipe:  Abbreviation for Chlorinated Polyvinyl Chloride Pipe, a high performance plastic pipe used for hot and cold-water distribution. CPVC pipe is commonly used for sprinkler pipe.
  • CSI:  Construction Specifications Institute
  • cUL (UL certifications for Canada):  An independent testing laboratory that also provides full product listing and follow-up services.
  • cULus Mark:  An Underwriters’ Laboratories certification mark that indicates compliance with both Canadian and U.S. requirements.
  • Cure:  in sealants, the process by which a compound attains its intended properties through evaporation, chemical reaction, heat, radiation, or a combination
  • Curtain Wall:  A particular type of exterior wall construction generally used for modern high-rise buildings.  Wall in non-loadbearing and usually constructed of metal and glass.
  • Curtain Wall Joint:  Perimeter gap between the concrete floor slabs and the exterior wall construction (usually of metal or glass) in high rise buildings.
  • Cycle:  In acoustics, the cycle is the complete oscillation of pressure above and below the atmospheric static pressure.
  • Cycles Per Second:  The number of oscillations that occur in the time frame on one second. (See Frequency). Low frequency sounds have fewer and longer oscillations.
  • Damping:  Damping is the dissipation of vibratory energy in solid media and structures with time or distance. It is analogous to the absorption of sound in air. 
  • Decibel (dB) :  A dimensionless unit which denotes the ratio between two quantities that are proportional to power, energy or intensity. One of these quantities is a designated reference by which all other quantities of identical units are divided. The sound pressure level in decibels is equal to 10 times the logarithm (to the base 10) of the ratio between the pressure squared divided by the reference pressure squared. The reference pressure used in acoustics is 20 microPascals. 
  • Deflection:  Deflection is the distance an elastic body or spring moves when subjected to a static or dynamic force. Typical units are inches or mm.
  • Detail:  a technical drawing that includes instructions for installing systems
  • Detail Drawing: An architectural drawing showing section details of a through-penetration firestop assembly with installation instructions and other pertinent details given.
  • Diffusion:  The scattering or random reflection of a sound wave from a surface. The directions of reflected sound is changed so that listeners may have sensation of sound coming from all directions at equal levels.
  • Draft Stop: A material, device or construction installed to restrict the movement of air within open spaces of concealed areas of building components such as crawl spaces, floor- ceiling assemblies, and roof-ceiling assemblies and attics. 
  • Draftstopping:   Building materials installed to prevent the movement of air, smoke, gases and flame to other areas of the building through large concealed passages, such as attic spaces and floor assemblies with suspended ceilings or open web trusses.
  • DWV:  Acronym for Drain, Waste, and Vent. Also referred to as an open system. The pipe is empty, not pressurized. Pipes that are used in plumbing applications.
  • Eccentric:  Penetrating item that is offset to one side of a through-penetration hole such that the annulus varies around the penetrating item.
  • Echo:  Reflected sound producing a distinct repetition of the original sound. Echo in mountains is distinct by reason of travel after original signal has ceased.
  • Elasticity:  the ability of a material to return to its original shape
  • Elastomeric:  Flexible, low modulus material capable of expanding and contracting and returning to original dimensions without fatigue.
  • Elastomeric material - Rubbery type of material that when stretched directionally will elongate. When the pressure is released will go back to its original shape, size and not lose its properties or characteristics. (like an elastic band)
  • EMT:  Abbreviation for Electrical Metal Tubing; conduit. Thin wall galvanized steel pipe, containing electric cables and wires.
  • Endothermic - Pertaining to or produced from the absorption of heat. A change that takes place with absorption of heat and requires high temperature for initiation and maintenance.
  • Endothermic Reaction:   Absorption of energy during a chemical reaction. Thus feeling cool to the touch.
  • Engineering Judgments:  To meet actual field conditions, manufacturers may need to make a recommendation based on available testing that seems to approximate the condition encountered. Testing laboratories should verify judgments by manufacturers for validity. Some jurisdictions only allow judgments if there is no tested system available for the condition.
  • ENMT:  Acronym for Electrical Nonmetallic Tubing
  • Exothermic Reaction:   The production of energy during a chemical reaction. Thus feeling warm to the touch.
  • Expansion Joint:  A structural separation between building elements that allows movement without damaging the structure
  • Exposed Side:  The exposed surface of an assembly refers to the surface facing the fire during a test.
  • F Rating (in the United States):  The time in hours that a firestop system will prevent the passage of flames through an opening and not permit the projection of water stream through a fire rated assembly as determined by standard test methods ASTM E- 814, UL 1479 or CAN/ULC S115.
  • FH Rating (in Canada):  The time in hours that a firestop system will prevent the passage of flames through an opening in a fire rated assembly as determined by standard test methods CAN/ULC S115.
  • Field Erected System:  Firestop materials assembled at the jobsite into a particular configuration utilizing materials that are intended to lend themselves to a variety of different conditions.
  • Fill Material:  Firestopping material used to fill within the penetration. Fire Compartment of Fire Zone: An enclosed space in a building that is separated from all other parts of the building by the construction of Fire Separations having Fire Resistance Ratings.
  • Fill, Void or Cavity Material:   A firestop material (e.g. sealant, putty, mastic, etc.)
  • Fire Area:  The aggregate floor area enclosed and bounded by building separation walls, fire barrier walls, exterior walls or fire-resistance rated horizontal assemblies of a building.
  • Fire Barrier:  A continuous membrane, either vertical or horizontal, such as a wall or floor assembly that is designed and constructed with a specified fire resistance rating to limit the spread of fire and restrict the movement of smoke.
  • Fire Barrier Wall:  A fire-resistance rated assembly of materials having protected openings which is designed to restrict the spread of fire. 
  • Fire Blocking:   Building materials installed to resist the free passage of flame to other areas of the building through concealed spaces.
  • Fire Compartment:  A space, within a building, that is enclosed by fire barriers on all sides, including the top and bottom.
  • Fire Damper:  A device, installed in an air distribution system, designed to close automatically upon detection of heat, to interrupt migratory airflow, and to restrict the passage of flame. A combination fire and smoke damper meets the requirement of both.
  • Fire Door: The door component of a fire door assembly.
  • Fire Door Assembly:  Any combination of a fire door, frame, hardware, and other accessories that together provide a specific degree of fire protection to the opening.
  • Fire Partition:   A vertical assembly of materials, having protected openings, designed to restrict the spread of fire.
  • Fire Resistance:  That property of materials or their assemblies which prevents or retards the passage of excessive heat, hot gases or flames under conditions of use.
  • Fire Resistance Rating:   The period of time a building or buildings component maintains the ability to confine a fire or continues to perform a structural function or both. This is usually determined or measured by ASTM E-119 test standard.
  • Fire Resistive:  Have a resistance to fire.
  • Fire Resistive Joint System:   A system consisting of specified materials designed and tested to resist the passage of flame and hot gases sufficient to ignite cotton waste for a prescribed period of time in accordance with UL 2079.
  • Fire Risk:  The probability that a fire will occur. The potential for risk to life or property.
  • Fire Separation:  A construction assembly that acts as a barrier against the spread of fire.
  • Fire Separation Distance:  The distance in feet measured from the building face to the closest interior lot line, to the centerline of a street, alley or public way, or to an imaginary line between two buildings on the property.
  • Fire Separation Wall:  See “fire barrier wall.” Transitional term replaced by “fire barrier wall.”
  • Fire Wall:  1. A wall constructed of solid masonry units, faced on each side with brick or reinforced concrete, used to subdivide a building or separate buildings, to restrict the spread of fire. 2. A wall with adequate fire resistance used to subdivide buildings to restrict the spread of fire.
  • Fire Window:  A window constructed and glazed to give protection against the passage of fire.
  • Fireblocking:  Building material installed to resist the free passage of flame and gases to other areas of the building through small concealed spaces.
  • Fire-rated:  the property of a material or assembly to withstand fire or give protection from it.
  • Fire-Resistive Joint System – is an assemblage of specific material or products that are designed, tested and fire-resistive in accordance with UL 2079 to resist, for a prescribed period of time, the passage of fire through points made in or between fire resistance-rated assemblies.
  • Fire-Retardant Barrier: A layer of material, which, when secured to a combustible material or otherwise interposed between the material and a potential fire source, delays ignition and combustion of the material when the barrier is exposed to fire.
  • Fire-Retardant Chemical: A chemical, which, when added to a combustible material, delays ignition and combustion of the resulting material when exposed to fire.
  • Fire-Retardant Coating: A fluid-applied surface covering on a combustible material that delays ignition and combustion of the material when the coating is exposed to fire.
  • Fire-Retardant Treatment: The use of a fire-retardant chemical or a fire-retardant coating.
  • Firestop:  a through-penetration firestop is a specific construction consisting of all materials that fill the opening around penetrating items such as cables, cable trays, conduits, ducts, and pipes and their means of support through the wall or floor to prevent the spread of fire. (ASTM)
  • Firestop Devices:  Firestop materials assembled into their final form at the point of manufacture.  Example:  Firestop Collars
  • Firestop System:  A specific construction consisting of a fire rated assembly (wall or floor), penetrating item(s) (pipe, cable, etc.), and materials (sealant, backing material, etc.) that fill the opening around penetrating item(s) to prevent the spread of fire beyond the assembly for a specified period of time.
  • Flame Front:  The leading edge of a flame propagating through a gaseous mixture or across the surface of a liquid or solid.
  • Flame:  A hot, usually luminous zone of gas, or particulate matter in gaseous suspension, or both, that is undergoing combustion.
  • Flame Resistance:  The ability to withstand flame impingement or provide protection against it.
  • Flame Spread Index:  A number or classification showing a comparative measure derived from observations made during the progress of the boundary of a zone or flame under defined test conditions.
  • Flame Spread:  Classification indicating propagation of flame across a sample compared to flame propagation across concrete panels and red oak.  Results are obtained through an ASTM E84 or UL 723 test.
  • Flame-Resistant:  Having resistance to flame.
  • Flammable:  Subject to easy ignition and rapid flaming combustion.
  • Flammable Vapor:  The vapor given off by a flammable liquid at, and above, its flash point.
  • Flanking:  The transmission of sound around the perimeter or through holes within partitions (or barriers) that reduces the otherwise obtainable sound transmission loss of a partition. Examples of flanking paths within buildings are ceiling plena above partitions; ductwork, piping, and electrical conduit penetrations through partitions; back-to-back electrical boxes within partitions, window mullions, etc.
  • Flash Point:  The lowest temperature of a sample at which application of an ignition source causes the vapor of a sample to ignite momentarily under specified conditions of test.
  • Flutter Echo:  Short echoes in small reverberative spaces that produce a clicking, ringing or hissing sound after the original sound signal has ceased. Flutter echoes may be present in long narrow spaces with parallel walls.
  • FM 4991:  FM Global 4991 standard is a quality control program that allows tracking of firestop installers via a certification program. 
  • Foam Core:  Various nonmetallic pipes where porosity has been induced into the pipe's cross section to reduce weight and cost.  Sometimes referred to as coax piping.
  • Forming Materials:  Materials used under or beside a firestop system to either hold the system in place during application, improve fire resistance, or both. Mineral wool, ceramic fiber and other materials are used. Consult the manufacturer’s specific tested system data for type, thickness and density of material allowed.
  • Free Field:  Sound waves from a source outdoors where there are no obstructions.
  • Free Expansion:  Non-restricted expansion
  • Frequency:  The number of oscillations or cycles per unit of time. Acoustical frequency is usually expressed in units of Hertz (Hz) where one Hz is equal to one cycle per second.
  • Frequency Analysis:  An analysis of sound to determine the character of the sound by determining the amount of sounds at various frequencies that make up the overall sound spectrum. For example, higher frequency sound or pitch vs. low frequency. 
  • FRPP:  Acronym for Fire-Retardant Polypropylene.  A combustible thermoplastic resin used in the manufacture of certain nonmetallic pipes used primarily for high-end DWV applications such as acid waste lines.
  • Ga:  Abbreviation for Gauge.
  • Galv:  Abbreviation for Galvanized.
  • Glass Fiber Board:  Fibrous glass insulation consisting of inorganic glass fibers formed into rigid boards using a binder.
  • Glow: 1. The visible light emitted by a substance because of its high temperature. 2. Visible light, other than from flaming, emitted by a solid undergoing combustion.
  • GWB:  Abbreviation for Gypsum Wall Board; Type X gypsum wallboard manufactured to provide specific fire-resistive characteristics. (GWB type X, 5/8” thick has a 30-minute fire resistive rating).
  • Gypsum Wallboard Type X:  A mill fabricated product made of a gypsum core containing special minerals and encased in a smooth, finished paper on the face side and line paper on the back.
  • Head-Of-Wall:  The gap between the top of a wall assembly and the lower surface of the floor assembly above it.
  • Hearing Impairment:  A degree of hearing loss, temporary or permanent, due to many causes. Hearing loss can be caused by illness, disease, or exposure to excessively high noise levels. Affects 25 – 50 million people in USA of all ages. Hearing impairment as generally used means a hearing loss of mild, moderate or severe degree as opposed to “deafness” which is generally described as little or no residual hearing with or without the aid of an assistive listening device. Hearing impaired persons are particularly adversely affected by long reverberation times.
  • Hearing Range:  16 – 2000 Hz (Speech Intelligibility), 600 – 4800 Hz (Speech Privacy), 250 – 2500 Hz (Typical small table radio)
  • Heat Transmission Endpoint:  An acceptance criterion of ASTM E 119 limiting the temperature rise of the unexposed surface temperature to an average of 250°F or a maximum of 325°F at any one point.
  • Hertz (Hz):  Frequency of sound expressed by cycles per second. (See Cycle).
  • Hose Stream Test:  Part of the acceptance criteria of ASTM E119, ASTM E814, CAN4 S115, UL 2079. After the test assembly has passed the furnace burn, a steady stream of water is directed onto the fire exposed side of the assembly through a 2 ½” hose. Water is not permitted to pass through the firestop fill material to the unexposed side. The integrity of the unexposed side must remain intact.
  • I.T.S. (Warnock Hersey):  Independent third party testing laboratory located in Coquitlam, B.C. and Pittsburg, CA for firestop testing. Proper company name is Intertek Testing Services (ITS)
  • Ignition:  The initiation of combustion.
  • Ignition Temperature:  The lowest temperature at which sustained combustion of a material can be initiated under specified conditions.
  • Intensity:  See Loudness.
  • International Conference of Building Officials (ICBO):  Publishes Uniform Building Code (UBC). It is principally used in the Western portions of the United States.
  • Intumesce:  To swell, enlarge, inflate, or expand with heat. Intumescent firestopping sealants swell when exposed to the intense heat of fire to close gaps or voids in through-penetration openings.
  • Intumescence:  A characteristic of certain fire barrier products that, when exposed to heat, expands to fill a void in the penetration caused by the deformation or combustion of the through penetrating item. When exposed to heat, intumescent materials expand at various rates to form a hard char to seal voids and provide hourly rated protection.
  • Intumescent:  A material that swells or expands when exposed to direct flame or high heat (300° F, 150°C). Produced for firestopping materials in several forms; caulks, pipe collars, wrap strips, sticks and pads. Most common usage is to close gaps and voids when plastic pipe has melted.
  • Inverse Square Law:  Sound levels fall off with distance traveled. Sound level drops off 6 dB from the source point for every doubling of distance.
  • ISMA Structure:  Intermediate Scale Multi-Story Testing Apparatus.  Furnace structure designed to simulate a fire in a high rise building.  Subjects a rated floor, nonrated curtain wall and the perimeter joint treatment to a fire exposure from two sides simultaneously.
  • Joint or Gap:  The linear opening in or between adjacent fire-resistance rated assemblies that is designed to allow independent movement of the building, in any plane, caused by thermal, seismic, wind loading or any other loading.
  • Joint System:  A joint system is a specific construction consisting of adjacent wall and/or floor assemblies and the materials designed to help prevent the spread of fire through a linear opening between the wall and/or floor assemblies.
  • Joint Treatment:  Materials installed within a joint to provide a level of fire-resistance equal to that of the lesser of the two substrates it is installed between.
  • Joints: Gaps between two or more adjoining surfaces, left to provide for expansion and contraction of the assembly.
  • L Rating:  An optional test performed to determine the amount of air leakage through a firestop system (in cubic feet per minute per square foot of opening) Tested in conjunction with UL 1479, ULC S115-M95, ASTM E 814 or UL 2079.
  • Latex:  A water emulsion of a synthetic rubber material that is manufactured into a sealant.
  • Lightweight Aggregate Concrete:  Concrete made with aggregates of expanded clay, shale, slag or sintered slate or fly ash, and weighing 85 to 115 pcf.
  • Linear Opening:  A discontinuity between or within fire resistive structures.
  • Listed System Design:  An informational listing by an Accredited Testing Agency developed from manufacture reports depicting the correct use and installation of firestop materials. These published listings contain drawings depicting geometry, minimum/maximum dimensions for all the individual components tested including penetration item types and size, annular space, insulating materials used, substrate types and thickness, sealant types and thickness, etc.
  • Live End/Dead End:  An acoustical treatment plan for rooms in which one end is highly absorbent and the other end is reflective and diffusive.
  • Loudness:  A listener’s auditory impression of the strength of a sound. The average deviation above and below the static value due to a sound wave is called sound pressure. The energy expended during the sound wave vibration is called intensity and is measured in intensity units. Loudness is the physical resonance to sound pressure and intensity.
  • Masking:  The process by which the threshold of hearing of one sound is raised due to the presence of another.
  • Mass:  Mass is the fundamental property of a material relevant to sound transmission loss through that material. Generally, the more massive the material, the greater the sound transmission loss.
  • Maximum Joint Width:  The greatest width to which the joint system is designed to extend taking into consideration all axes of movement.
  • Membrane Penetration:  An opening made through one side (wall, floor or ceiling membrane) of an assembly.
  • Membrane Penetration Firestop:   A material, device or construction installed to resist, for a prescribed period of time when tested in accordance with appropriate test standard. The passage of flame and heat through openings in a protective membrane in order to accommodate cables, cable trays, conduit, tubing, pipes or similar items.
  • Mineral Board: A rigid thermal insulation board consisting of either felted mineral fiber or cellular beads of expanded aggregate.
  • Mineral Fiber:  a noncombustible insulation material - sometimes referred to as mineral wool or safing
  • Mineral Wool or Rock Wool:  A fire-resistant fibrous material used as a insulation and filler material in a firestop system, capable of withstanding temperatures of 1832 deg. F (1000 deg. C) Supplied in loose and blanket board form. The most popular used for firestopping is 4 and 6-lb batts, 24” x 48” (8-lb is fairly rigid and is usually used in larger construction joints).
  • Minimum Joint Width:  The narrowest width the joint system is designed to accommodate.**
  • Modulus:  A term used to describe the elasticity of sealants.  The amount of pressure required to compress or stretch a cured sealant specimen.
  • Mounting:  Standards established by ASTM to represent typical installation for purpose of testing materials. For example, a mounting test specimen is mounted directly the test room surface or furred out to produce an air space behind.
  • Movement Capability:  The range of movement a joint is designed to accommodate without diminishing its fire resistive performance.
  • MSDS:  Material Safety Data Sheet - describes the properties, health effects, hazards, handling, and disposal of a material
  • NFPA: National Fire Protection Association, based in Quincy, Mass., author of “The Life Safety Code.”
  • Noise:  Unwanted sound that is annoying or interferes with listening. Not all noise needs to be excessively loud to represent an annoyance or interference.
  • Noise Criteria (NC):  Noise criteria curves used to evaluate existing listening conditions at ear level by measuring sound levels at the loudest locations in a room. NC criteria can be referred to equivalent dBA levels.
  • Noise Isolation Class (NIC):  A single number rating of the degree of speech privacy achieved through the use of an Acoustical Ceiling and sound absorbing screens in an open office. NIC has been replaced by the Articulation Class (AC) rating method.
  • Noise Reduction (NR):  The amount of noise that is reduced through the introduction of sound absorbing materials. The level (in decibels) of sound reduced on a logarithmic basis.
  • Noise Reduction Coefficient (NRC):  The NRC of an acoustical material is the arithmetic average to the nearest multiple of 0.05 of its absorption coefficients at 4 one-third octave bands with center frequencies of 250, 500, 1000, 2000 Hertz. The NRC rating can be viewed as a percentage (example: .80 = 80%) of what soundwaves that come in contact with the acoustical material are absorbed by the material and NOT reflected back within the room.
  • Noncombustible:   A material that, in the form in which it is used and under the conditions anticipated, will not aid combustion or add appreciable heat to an ambient fire.
  • Non-Rated System:  An assembly that has not been tested, or assigned an hourly rating in accordance with ASTM E-119.
  • Non-Sag Caulk:  Any compound that does not flow or sag out after application usually installed in a vertical joint or wall penetration.
  • Nonvented:  Piping systems that do not allow the free passage of air, e.g., hot and cold water supply pipes, electrical conduits. Also referred to as closed.
  • Normal Weight Concrete:  Any concrete made with natural aggregates, cement and water having a unit weight of approximately 150 pcf.